©Johnstone Supply eCatalog 216
HVAC EQUIPMENT Coleman Heat Pumps
Heat Pumps LX Series, 16 SEER, Single-Phase, 1-1/2 to 5 Ton, R410A
• Aluminum fin and copper tube outdoor coil • Removable 2-piece steel extruded louver coil guard
• Easy service access • Adapter fitting required for 1-1/8" line set • 208/230V Applications: • Product not suitable for all regions Warning: Cancer and Reproductive Harm - www.P65Warnings.ca.gov Note: Installation must meet all Federal, State, and Local guidelines
• 1-Stage scroll compressor • Factory installed filter-drier • TXV controls to all indoor coils • Suction accumulator • Demand defrost • High & low pressure switches • Conventional controls
BtuH Cooling
BtuH Heat ing Input
Min. Circuit Amps
Max. Fuse Size
Suction Fitting
Order #
Mfg. #
Nom. Tons
HSPF
Liquid Conn.
Width
Height
Depth
Wt. Lbs.
OEM TXV B19-657 B19-657 B19-657 B19-658 B19-659 B19-659 B19-660
B61-215 B61-216 B61-217 B61-218 B61-219 B61-220 B61-221
CH6B1821S 1-1/2
18,000 18,000 9.0 24,000 24,000 9.0 30,000 30,000 9.0 36,000 36,000 9.0 42,000 42,000 9.0 48,000 48,000 9.0 60,000 60,000 9.0
14.0 15.5 19.6 22.0 28.7 25.9 32.4
20 25 30 35 45 40 50
3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
3/4" 3/4" 3/4" 3/4" 7/8" 7/8"
29-1/4" 35-1/4" 35-1/4" 35-1/4"
36-1/4" 39-1/2" 39-1/2" 39-1/2" 39-1/2"
29-1/4" 31-3/4" 31-3/4" 31-3/4" 31-3/4" 34-1/4" 34-1/4"
136 176 176 223 270 292 304
CH6B2421S 2
CH6B3021S 2-1/2
CH6B3621S 3
CH6B4221S 3-1/2
38" 38" 38"
CH6B4821S 4 CH6B6021S 5
46" 46"
1-1/8"*
Horizontal Discharge Heat Pumps HMH7 Series, 17 SEER, Single-Phase, Modulating, 2 To 5 Ton, R410A • ECM motor • Modulating rotary compressor • Swept wing fan • Aluminum fin and copper tube outdoor coil
Applications: • Product not suitable for all regions Warning: Cancer and Reproductive Harm - www.P65Warnings.ca.gov Note: Installation must meet all Federal, State, and Local guidelines
• Field installed TXVs • Easy service access • 208/230V
BtuH Cooling
BtuH Heat ing Input
Min. Circuit Amps
Max. Fuse Size
Liquid Conn.
Suction Fitting
Order #
Mfg. #
Nom. Tons
HSPF
Width
Height
Depth
Wt. Lbs.
OEM TXV B19-657 B19-659 B19-659 B19-659
B64-413 B64-414 B64-415 B64-416
HMH72B241S 2 HMH72B361S 3 HMH72B481S 4 HMH72B601S 5
22,200 22,000 9 36,000 36,000 10.5 48,000 46,000 9.5 58,500 56,000 10
15 23 36 37
25 35 50 50
3/8" 3/8" 3/8" 3/8"
5/8" 3/4" 7/8" 7/8"
33-7/8" 37-3/8" 37-3/8" 37-3/8"
26-3/8"
12-1/4" 13-3/8" 13-3/8" 13-3/8"
112 148 227 251
33"
54-5/8" 54-5/8"
Heat Pumps Echelon™ 19 SEER, Single-Phase, Two-Stage, 2 To 5 Ton, R410A • Copper tube and aluminum fin coil • WhisperDrive™ System • 2-Stage scroll compressor • Swept-wing fan with ECM fan motor • Composite base pan • Factory installed filter-drier • Climate Connect™ • Hx thermostat • Communications capable • Suction accumulator • Compressor crankase heater • Compressor sound blanket
• Adapter fitting required for 1-1/8" line set • 208/230V Applications: • Product not suitable for all regions Warning: Cancer and Reproductive Harm - www.P65Warnings.ca.gov Note: Installation must meet all Federal, State, and Local guidelines
BtuH Cooling
BtuH Heat ing Input
Min. Circuit Amps
Max. Fuse Size
Liquid Conn.
Suction Fitting
Order #
Mfg. #
Nom. Tons
HSPF
Width
Height
Depth
Wt. Lbs. OEM TXV
B60-669 B60-670 B60-671 B60-672
HC19B2421S 2 HC19B3621S 3 HC19B4821S 4 HC19B6021S 5
24,000 24,000 9.5 36,000 36,000 10 48,000 48,000 9.6 60,000 60,000 9.6
15.3 21.4 28.2 31.4
25 35 45 50
3/8" 3/8" 3/8" 3/8"
3/4" 3/4" 7/8"
31-3/4" 34-1/2" 34-1/2" 34-1/2"
39-1/2" 46-1/2" 46-1/2" 46-1/2"
35-1/4" 38-1/4" 38-1/4" 38-1/4"
176 256 292 304
B19-658 B19-658 B19-659 B19-659
1-1/8" *
783
JohnstoneSupply.com
Made with FlippingBook Annual report maker