COMMERCIAL CONTROLS Pneumatics

Multi-Function Reset Volume Controllers • Pressure independent controllers for use with VAV terminal units • Velocity setpoint is reset between adjustable minimum and maximum limits by a master controller • Equipped with separate adjustment knobs for

• Includes mounting bracket • L40-187 is used with most all VAV units except Trane units • L40-188 is typically used with Trane VAV units Specifications: • Output sensitivity: L40-187 5 PSI/.02" w.g., L40-188 5 PSI/.04 w.g. • Main air pressure: 15 to 30 PSIG • Maximum signal pressure: 6" w.g. applied to either port (H or L) WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

minimum and maximum airflow setting • Multi-function for direct or reverse acting thermostats, and N.O. or N.C. damper actions • Reset start point is factory set at 8 PSIG (Adjustable 0-10 PSIG) • Reset span is factory set at 5 PSIG (adjustable 0-10 PSIG)

Each

Order #

Mfg. #

Description

Action

Air Consumption

L40-187 L40-188

CSC-3011-10 Differential Pressure: 0-1" wg CSC-3025-10 Differential Pressure: 0-2" wg

Cooling — DA / RA; Heating — DA / RA 28.8 SCIM @ 20 PSIG Cooling — DA / RA; Heating — DA / RA 46.1 SCIM @ 20 PSIG

439.00 439.00

Multiple Input Selector Relay • Selects and transmits the highest and/or lowest of up to six input signals • Low air capacity (for high capacity requirements, add a volume booster relay) • Mounting bracket included, can be mounted in-line

• Connections: 3/16" nipples for 1/4" O.D. polyethylene tubing WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Each

Order #

Mfg. #

Max. Pressure

Air Capacity 28.8 SCIM

Air Consumption

L40-203

RCC-1111

30 PSIG

28.8 SCIM

135.00

Relays • L40-199 and L40-204 reversing relays reverse the action of a proportional control signal, with adjustable offset to advance or retard cross over on both models • L40-199 has a 9 PSIG cross-over, L40-204 has an 8 PSIG cross-over, and they are for low capacity; for high capacity requirements, use L40-205 (RCC-1502) or L40-206 (RCC-1504) • L40-200 low pressure selector selects the lowest of two pneumatic signals and can be used as a signal repeating relay • L40-201 high pressure selector selects the highest of two pneumatic signals

• L40-202 diverting relay diverts input signal to either of two outputs or selects one of two inputs for the output signal and can be used to feed or exhaust a circuit (SPDT switch action) Specifications: • Max. pressure: 30 PSIG • Mounting bracket included, can be mounted in-line • Connections: 3/16" fittings for 3/4" O.D. polyethylene tubing WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

A

B

C

D

Each

Fig. Order #

Mfg. #

Description

Max. Pressure

Air Capacity

Air Consumption

L40-199 L40-200 L40-201 L40-202 L40-204

A B C D A

RCC-1101 Reversing Relay

30 PSIG 30 PSIG 30 PSIG 30 PSIG 30 PSIG

17.3 SCIM @ 20 PSIG 21.6 SCIM @ 20 PSIG

17.3 SCIM 21.6 SCIM

59.00 38.49 36.99

RCC-1106 Low pressure Selector RCC-1108 High Pressure Selector

260 SCIM @ 5 PSIG Pressure Drop

None None

RCC-1109 Diverting Relay RCC-1112 Reversing Relay

432 SCIM @ 20 PSIG 17.3 SCIM @ 20 PSIG

105.00

17.3 SCIM

69.00