©Johnstone Supply eCatalog 216
COMMERCIAL CONTROLS Pneumatics
Pneumatic Controllers • Proportional, high capacity, single or dual input controller • Used with remote sensors with output of 3 to 15 PSI to provide control of temperature, humidity, pressure or dewpoint for heating • Field reversible action and adjustable compensation start point • Integral action cut off provides trouble-free automatic startup • L40-043 has remote control point adjustment
Specifications: • Maximum supply air: 30 PSI @ 0.07 SCFM air capacity • Output signal: 3 to 13 PSI • Adjustable proportional band: 2.5% to 50% of primary sensor span • Integral reset time: 0.5 to 20 minutes, adjustable • Authority for L38-527 : 5% to 300% of span • Compensation start point for L38-527 : 0 to 100% of span • Air capacity: 0.07 SCFM
A
B
Each
Fig. Order # Mfg. #
Type
Air Consumption 0.021 SCFM 0.021 SCFM 0.046 SCFM
Dimensions
L40-043 RP920A1025 Single Sensor
A A B
3-13/16" W x 5-7/8" H x 3- 1/4" D without Cover x 3- 3/8" D with Cover 3-13/16" W x 5-7/8" H x 3-1/4" D without Cover x 3-3/8" D with Cover
1545.00 1445.00 1545.00
L38-526 L38-527
RP920A1033 Single Sensor RP920B1031 Dual Sensor
3-13/16" W x 5-7/8" H x 3-1/4" D
Velocitrol ® Velocity Sensor/Controllers • Ultra-sensitive air velocity sensor and pneumatic controller control pneumatic damper actuators in HVAC systems to provide constant air velocity in the duct regardless of the static pressure • Not position sensitive • Insensitive to static pressure changes • Graduated scales for minimum and maximum velocity adjustments
Specifications: • Airflow: Usage: 0.029 SCFM
• Humidity ratings: 5 to 95% RH (operating) • Pressure ratings: 18 to 20 PSI (operating); 30 PSI (maximum) • Operating temperature range: 40°F to 130°F • Sensor sensitivity: Less than 5 ft/min. maximum (no orifice) • Dimensions: Sensor is 1-3/4" W x 3-3/16" H x 4-3/16" long with orifice, 3-3/8" long without orifice; Controller is 3-1/4" W x 1-3/4" H x 2-3/8" D • Velocity range FPM 500; reset pressure 9 to 15 PSI
• Velocity reset by thermostat demand • Adaptable to many terminal unit control strategies • Dual Duct Variable Constant Volume application
Each
Order # Mfg. #
Description
For Use With
L39-850 CP980E1060 Direct, Sequencing, Sensor C Type
Normally Open Damper and Two-Pipe Thermostat Normally Closed Damper and Two-Pipe Thermostat
1999.00 1599.00
L39-851
CP980F1068 Reverse, Sequencing, Sensor C Type
Selector Relay • Three-port relays transmit the higher of two input signals, lock out one pressure signal when a second signal is higher, or transmit the lower of two pressure signals • Molded plastic construction includes mounting clip
Specifications: • Operating range: 0 to 18 PSI • Maximum supply air: 30 PSI • Air capacity: 0.039 SCFM @ 1 PSI differential • Dimensions: 1/2" diameter x 1" L
Each
Order # Mfg. #
Description
L38-523 RP470B1001
Lockout/Lower Pressure Selecting
165.00
Snap-Acting Relay • Four-port relay converts a proportional pressure change to a positive two-position pressure change • Molded plastic construction which includes mounting clip
Specifications: • Operating range: 0 to 18 PSI
• Setpoint: 3 to 15 PSI, adjustable • Differential: 1 PSI maximum, fixed • Maximum supply air: 30 PSI • Air capacity: 0.039 SCFM @ 1 PSI differential • Dimensions: 1-1/2" D x 2 -3/4" L
Each
Order # Mfg. #
L38-522 RP471A1002
455.00
414
©2023 Johnstone Supply, LLC
Made with FlippingBook Annual report maker